Function Name | Action | Factory setting |
Sleep Function | No water consumption pump decelerates to the lower limit and after a detection then sleep down. Until the pressure below settings, master wake up automatically. | valid |
Restarts After Power on | Power off during running, it restarts when power on again | invalid |
Anticlogging Function | Just designed for single pump, the pump run REV/FWD alternate. | invalid |
Day-Part Control | Devide one day into several day-part to run a private pressure respectively. Considered input side water pressure limit, once input water pressure is less than setting pressure, stop running; while up to setting, recover running. | invalid |
Terminal Run/Stop | Can be lead to external switch from terminal. When switch on, pump run and maintain a setting constant pressure; when switch off, pump stopped. | invalid |
Manual/Auto Control | Can be lead to external switch from terminal. When switch on, pump run with full-frequency; when switch off, return to variable frequency constant pressure control. | invalid |
Electric contact Control | Two terminals switch on COM instruct the controller to accelerate and decelerate respectively. Can used for realize the pump running in a switch setting pressure range. | invalid |
Model No. | Rated Input Voltage(V) | House Power(HP) | Rated Output Current(A) | Motor Power(KW) |
B601D-2001 | 1AC: 220V -15%~+15% |
1.0 | 5.3 | 0.75 |
B601D-20015 | 1.5 | 6.5 | 1.1 | |
B601D-2002 | 2 | 9.6 | 1.5 | |
B601D-2003 | 3 | 14 | 2.2 |
Model (kW) |
A (mm) | B (mm) | H (mm) | W (mm) | D (mm) | Installation Hole | |
Installation Dimension | External Dimension | ||||||
0.75~2.2 | 110 | 169.6 | 179.6 | 120.1 | 150.3 | 4.0 |
Function Code | Name | Setting Range | Factory Setting | Description |
Group br00 Application Group | ||||
b00.00 | Debugging password | 0~65535 | 00000 | Parameter group password, can be changed by b06.09, default is 65535 |
b00.01 | Pressure setting value | 0.0~100.0 | 3.0bar | Set according to the actual requirements of user |
b00.02 | Motor rotating direction | 0,1 | 0 | 0: forward 1: reverse |
b00.03 | Reserved | |||
b00.04 | Anti-clogging | 0,1 | 0 | 0: invalid 1: valid Prevention measures, auto reset after stop the running pump. |
b00.05 | Anti-clogging rotating cycle | 0.0~300.0s | 0.0 | When the anti-clogging function is valid, used to set the forward/reverse rotating direction cycle and corresponding output frequency (frequency setting value should be lower than the rated frequency of the pump so as not to cause damage) |
b00.06 | Anti-clogging output frequency | 0.00~600.00HZ | 30.00Hz | |
Group br01 Running Parameter Group | ||||
b01.00 | High Water Pressure/Level Alarm Value | 0.0~100.0 | 10.0bar | When pressure is higher than this preset value, the pump halts, alarms and displays HP. |
b01.01 | Low Water Pressure/Level Alarm Value | 0.0~100.0bar | 0.5bar | When pressure is lower than the preset value for a Low Pressure Running Time, the pump halts,alarms and displaying LP. |
b01.02 | Low Pressure/Level Running Time | 0~60s | 10s | |
b01.03 | Reserved | |||
b01.04 | Anti-clogging FWD./REV. Dead Time | 0.0~3600.0 | 1.0s | When anti-clogging is valid, b01.04 set the FWD./REV. transition time |
b01.05 | Maximum Transducer Setting Range | 0.0~100.0 | 10.0 | E.g. If the rated max. range of transducer is 10Bar, b01.05 should be set to 10.0 |
b01.06 | AI1 Lower Limit | 0.00~10.00V | 0.00V |
Figure4-1-1 Transducer Parameters |
b01.07 | Corresponding Setting of AI1 Lower Limit | -100~100% | 0% | |
b01.08 | AI1 Higher Limit | 0~10V | 5V | |
b01.09 | Corresponding Setting of AI1 Higher Limit | -100~100% | 100% | |
b01.10 | AI1 Filtering time | 0.00~10.00s | 0.10s | |
b01.11 | AI2 Lower Limit | 0~10V | 0V | |
b01.12 | Corresponding Setting of AI2 Lower Limit | -100~100% | 0% | |
b01.13 | AI2 Higher Limit | 0~10V | 5V | |
b01.14 | Corresponding Setting of AI2 Higher Limit | -100~100% | 100% | |
b01.15 | AI2 Filtering time | 0.00~10.00s | 0.10s | |
b01.16 | Restart After Power-on | 0,1 | 0 | 0:invalid 1:valid |
b01.17 | Control mode | 0,1 | 0 | 0:synchronous 1:master-slave |
GROUP br02 PID PARAMETER GROUP | ||||
b02.00 | PID Source Selection | 0,1 | 0 | 0:Keypad 1: Communication |
b02.01 | PID Feedback Source Selection | 0~2 | 0 | 0:AI1 1:communication 2:Reserved |
b02.02 | PID Output Characteristics | 0,1 | 0 | 0:water Supply 1:pumping |
b02.03 | Proportional Gain (Kp) | 0.00~100.00 | 0.60 | Determining the strength of PID regulation, Kp is bigger, regulation is stronger, but fluctuate easier too. |
b02.04 | Integral Time (Ti) | 0.01~10 | 0.30s | Bias between the Feedback and the Given, determining the speed of regulation, a shorter Ti gains a stronger regulation. |
b02.05 | Differential Time (Td) | 0.00~10 | 0.00s | Variable Ratio between the Feedback and the Given, a longer Td gives a stronger regulation. Be cautious use, for differential regulation amplifies interference of system. |
b02.06 | Sampling Cycle (T) | 0.01~100.00 | 0.10s | Calculating time of regulator, when increased, response sluggishly. |
b02.07 | PID Control Bias Limit | 0.0~100% | 0.00% | Max. Bias of PID output value corresponding to closed loop given value; Corresponding System Diagram of Max. Limit and Output Frequency. Figure4-2-1 PID control curve Properly set the value can regulate the accuracy and stability of PID system. |
b02.08 | AI1 Feedback Lost Detecting Value | 0.0~100.0% | 1.0% | Transducer Fault Detecting Setting Value, corresponding to full range(100%), when the detecting time exceeds Feedback Lost time, it is deemed as malfunction by Transducer, the system will report E022 as Transducer Fault Code |
b02.09 | AI2 Feedback Lost Detecting Value | 0.0~100.0% | 0.0% | |
b02.10 | Feedback Lost Detecting time | 0.00~3600s | 1.00s | |
Group br03 Communication Parameter Group | ||||
Multi-pump control temporary reserved, do not modify this group. | ||||
Group br04 Sleeping Function Group | ||||
b04.00 | Sleeping Function | 0,1 | 1 | No consuming auto stop. 0:invalid 1:valid |
b04.01 | Sleeping Waiting time | 0.0~300.0s | 5.0s | delay time, seconds unit |
b04.02 | Sleeping Test Freq. proportion | 0~100% | 4% | Ensure Halt frequency when no consuming, the value corresponds the rated frequency, e.g. rated frequency50Hz×4%=2Hz, spot setting 1%~4% as proper. |
b04.03 | Wake-up Pressure Bias | 0.0~20.0bar | 0.5bar | During sleeping waiting time, when the practical outlet pressure is lower than the setting pressure, that is, b00.00 subtracts Wake-up Pressure Bias, the pump restart to work automatically, e.g. the setting value(L)=3.0Bar, Bias(b04.03)=0.5bar, Practical pressure(P)≤L-0.5=2.5bar, the pump will restart to work automatically again. |
Group br05 Control Parameter Group | ||||
b05.00 | Water Level Control (Terminal S3) |
0~2 | 1 | Water level switch style, 0:invalid 1:NC 2:NO |
b05.01 | S3 Action Delay Time | 0~300min | 0 | Delay time after level switch on, the time can not be set shortly or will create fluctuation caused by frequent initiate-stop. |
b05.02 | Terminal S1S2 Control | 0~3 | 0 | 0: invalid 1: Electric contact control S1-COM on: Frequency rise S2-COM on: Frequency drop 2: Manual/auto control S2-COM off: auto control S2-COM on: manual control 3: Terminal run/stop S1-COM on: Run S1-COM off: Stop S2-COM off: auto control S2-COM on: manual control Auto Control: Constant water pressure control Manual Control: Full frequency Running |
b05.03 | Acceleration Time | 0.1~3600s | Model set | The setting time from max. Frequency to zero. |
b05.04 | Deceleration Time | 0.1~3600s | Model set | The setting time from zero to max. Frequency |
b05.05 | Maximum Output Frequency | 10.00~600.00Hz | 50.00Hz | Determine the Acc./Dec. rate |
b05.06 | Up limit of Output Frequency | 00.00~b05.05(Max. Frequency) | 50.00Hz | Maximum running frequency |
b05.07 | Lower Limit of Output Frequency | 0.00~600.00Hz | 30.00Hz | The setting in order to guarantee High Efficiency of water pump, depend on the features of the pump, advise that the setting value is selected from 30.00Hz to 40.00Hz. |
b05.08 | Carrier Frequency | 1.0~15.0kHz | Model Set | Use to ameliorate the noise of motor and controller's interference to the surroundings. A high carrier makes a low motor noise, but leads to a big temperature rise and interference. Should not be altered if unnecessary. |
b05.09 | Low Pressure(LP) Restart Delay Time | 0.0~300.0min | 0.0 | In case of Low Pressure, BR5.09≠0,the controller restart to work according to the setting time automatically, without artificial restart. BR5.09=0, means auto restart invalid. |
b05.10 | Alternating Time 0.0:invalid | 0.0~600.0h | 0.0 | In order to balance and prolong the pump service life to set the parameter, Unit: hour, when the parameter is set to 0.0, it means in-execution. Operational time of master and auxiliary pump switches over according to the setting Alternating Time. |
Group br06 Interface Parameter Group | ||||
b06.00 | Running Status Display Selection | 0~0x1FF | 0x01F | bit0: Operational Frequency bit1: Pressure tested value bit2: Pressure setting value bit3: Output Current bit4:Busbar Voltage bit5:Output Voltage bit6:Present Time bit7: Inlet Pump Pressure bit8: Master Sending Frequency |
b06.01 | Stop Status Display Selection | 0~0x1FF | 0x00F | bit0: Pressure setting value bit1: Pressure tested value bit2: Setting Frequency bit3: Busbar Voltage bit4: Input Terminal Status bit5:Output Terminal Status bit6:AI1 Input Voltage bit7: Inlet Pump Pressure bit8: Present Time |
b06.02 | Keypad Display Selection | 0~3 | 0 | 0:External Keypad Prior Enable 1:Both Display Enable, Only External Keypad Control; 2:Both Display Enable, Only Onboard Keypad Control; 3:Both Display Enable and Keypad Control. |
b06.03 | Relay Output Selection | 0~4 | 0 | 0:Error or External Fault 1:Forward Running 2:Frequency Reaching 3:Stop Status 4:Lower Limit of Output Frequency Reaching |
b06.04 | Third Latest Fault Type | Read Only | E000:Fault-free E001:INU U phase protection E002:INU V phase protection E003:INU W phase protection E004:Acceleration OC E005:Deceleration OC E006:Constant Velocity OC E007:Acceleration OV E008:Deceleration OV E009:Constant Velocity OV E010:Busbar Under voltage E011:Motor Overload E012:Controller Overload E013:Input Phase Failure E014:Output Phase Failure E015:Rectifier Module Overheat E016:Inversion Module Overheat E017:Outside Fault E018:Communication Fault E019:Current Sense Fault E020: Reserve E021:EEPROM Operation Fault E022:Transducer Fault E023:Reserve E024:Reserve |
|
b06.05 | Second Latest Fault Type | |||
b06.06 | Latest Fault Type | |||
b06.07 | Parameters Storage Condition | 0~2 | 0 | 0:Power-off Storage 1:Power-off default storage 2:invalid |
b06.08 | Accumulated Running Time | 0~65535h | Read Only | Display Accumulated Running Time |
b06.09 | Set the Password of br00.06 | 0~65535 | 65535 | Password set prevent user from modifying the parameters randomly, avoiding running abnormally and damages. |
Group br07 Day-part Water Supply Parameter Group | ||||
b07.00 | Day-part Function Selection | 0~3 | 0 | 0:invalid 1:day-part A 2:day-part A and B 3:day-part A, B, C |
b07.01 | Day-part A Starting Time | 00.00~24.00 | 0 | Setting Starting Time and Finishing Time to 0 is invalid. Pressure Setting determines the steady state value of outlet pressure. Once actual pressure from inlet pipe network lower than setting lower limit pressure value such as b07.04, the pump stops till it rise up to lower limit pressure value again. When regardless of the inlet water pressure, just set the lower limit as 0. |
b07.02 | Day-part A Pressure Setting | 0~20bar | 3.0bar | |
b07.03 | Day-part A Finishing Time | 00.00~24.00 | 0 | |
b07.04 | AI2 Lower Limit of Day-part A | 0~20bar | 2.0bar | |
b07.05 | Day-part B Starting Time | 00.01~24.00 | 0 | |
b07.06 | Day-part B Pressure Setting | 0~20bar | 3.0bar | |
b07.07 | Day-part B Finishing Time | 00.00~24.00 | 0 | |
b07.08 | AI2 Lower Limit of Day-part B | 0~20bar | 3.0bar | |
b07.09 | Day-part C Starting Time | 00.00~24.00 | 0 | |
b07.10 | Day-part C Pressure Setting | 0~20bar | 3.0bar | |
b07.11 | Day-part C Finishing Time | 00.00~24.00 | 0 | |
b07.12 | AI2 Lower Limit of Day-part C | 0.0~20.0bar | 3.0bar | |
b07.13 | Lower Limit of Inlet Pressure | 0~20bar | 0.0bar | Valid all day, especially for the use of testing inlet pressure, when needn't the inlet pressure limit set as 0. |
b07.14 | Restore Defaults | 0~2 | 0 | 0:No action 1:Set to default 2:Clear error records |
b07.15 | Password of Group br08 | 0~65535 | 00000 | Decide by b08.06, default of b08.06 is 65535. |
Group br08 Motor Parameter Group | ||||
b08.00 | G/P Option | 0,1 | 0 | 0:G model 1:P model |
b08.01 | Motor Rated Power | 0.4~93kw | Model Set | Setting parameters according to nameplate of Motor. The controller's OV, OC protection base on the parameters of this group. |
b08.02 | Motor Rated Frequency | 0.01~600Hz | 50Hz | |
b08.03 | Motor Rated Speed | 0~36000RPM | Model Set | |
b08.04 | Motor Rated Voltage | 0~460V | ||
b08.05 | Motor Rated Current | 0.1~2000A | ||
b08.06 | Password of br07.15 | 0~65535 | 65535 | Modify password of BR7.15 |
b08.07 | Password of Factory Parameters | 0~65535 | xxxxx | Don't have a try or will cause abnormal operation and damages. |