Model No. | Rated Input Voltage (V) | Input Current (A) | Max. Output Current (A) | Motor Power (kW) |
B603D(B)-2001 | 1AC: 220V -15%~+15% |
8.2 | 4.5 | 0.75 |
B603D(B)-2002 | 14.2 | 7.0 | 1.5 | |
B603D(B)-2003 | 23.0 | 10.0 | 2.2 | |
B603D-2001 | 3AC: 220V -15%~+15% |
5.0 | 4.5 | 0.75 |
B603D-2002 | 7.7 | 7.0 | 1.5 | |
B603D-2003 | 11.0 | 10.0 | 2.2 | |
B603D(B)-2005 | 17.0 | 16.0 | 3.7 | |
B603D(B)-2007 | 21.0 | 20.0 | 5.5 | |
B603D-2010 | 31.0 | 30.0 | 7.5 | |
B603D-2015 | 43.0 | 42.0 | 11 | |
B603D-2020 | 56.0 | 55.0 | 15 | |
B603D-2025 | 71.0 | 70.0 | 18.5 | |
B603D-2030 | 81.0 | 80.0 | 22 | |
B603D-2040 | 112.0 | 110.0 | 30 | |
B603D-2050 | 132.0 | 130.0 | 37 | |
B603D-2060 | 163.0 | 160.0 | 45 | |
B603D-2075 | 200.0 | 200.0 | 55 | |
B603D(B)-4001 | 3AC: 380V -15%~+15% |
3.4 | 2.5 | 0.75 |
B603D(B)-4002 | 5.0 | 3.7 | 1.5 | |
B603D(B)-4003 | 5.8 | 5.0 | 2.2 | |
B603D(B)-4005 | 10.0 | 9.0 | 4.0 | |
B603D(B)-4007 | 15.0 | 13.0 | 5.5 | |
B603D(B)-4010 | 20.0 | 17.0 | 7.5 | |
B603D(B)-4015 | 26.0 | 25.0 | 11 | |
B603D(B)-4020 | 35.0 | 32.0 | 15 | |
B603D-4025 | 38.0 | 37.0 | 18.5 | |
B603D-4030 | 46.0 | 45.0 | 22 | |
B603D-4040 | 62.0 | 60.0 | 30 | |
B603D-4050 | 76.0 | 75.0 | 37 | |
B603D-4060 | 90.0 | 90.0 | 45 | |
B603D-4075 | 105.0 | 110.0 | 55 | |
B603D-4100 | 140 | 150 | 75 | |
B603D-4120 | 160 | 176 | 90 | |
B603D-4150 | 210 | 210 | 110 | |
B603D-4180 | 240 | 250 | 132 | |
B603D-4215 | 290 | 300 | 160 | |
B603D-4250 | 330 | 340 | 185 | |
B603D-4270 | 370 | 380 | 200 | |
B603D-4300 | 410 | 415 | 220 | |
B603D-4340 | 460 | 470 | 250 | |
B603D-4380 | 500 | 520 | 280 | |
B603D-4430 | 580 | 600 | 315 | |
B603D-4470 | 620 | 640 | 350 |
Function Code | Name | Setting Range | Factory Setting | Description | |||
Br00 Group Application Function | |||||||
b00.00 | Debugging Password | 0~65535 | 65535 | Decide by b06.09, default is 65535 | |||
b00.01 | Pressure Setting Value | 0.0~100.0bar | 3.0bar | Set according to the actual requirements of user | |||
b00.02 | Motor Rotating Direction | 0~1 | 0 | 0: Forward 1: Reverse | |||
b00.03 | Freeze-proofing | 0~1 | 0 | Used in cold areas 0: Invalid 1: Valid |
|||
b00.04 | Anti-clogging | 0~1 | 0 | Prevention measures 0: Invalid 1: Valid |
|||
b00.05 | Anti-clogging Rotating Cycle |
1.0~300.0s | 20.0s | Set the forward/reverse rotating direction cycle and corresponding output frequency (should not be higher than the rated frequency of the pump) of anti-clogging. | |||
b00.06 | Anti-clogging Output Frequency | 0.00~600.00 Hz |
15.00Hz | ||||
Br01 Group Application Function | |||||||
b01.00 | High Water Pressure/Level Alarm Value | 0.0~100.0bar | 8.0bar | When pressure is higher than this preset value, the controller halts, alarms and displays HP. | |||
b01.01 | Low Water Pressure/Level Alarm Value | 0.0~100.0 bar |
0.5bar | When pressure is lower than the preset value for a low pressure running time, the controller halts,alarms and displays LP | |||
b01.02 | Low Pressure/Level Running Time | 0~300s | 20s | ||||
b01.03 | Minimum Freeze-proofing Frequency | 1.00~30.00Hz | 5.00Hz | Be valid when b00.03 was set to 1, whenever sleeps, running with the setting frequency in case of freezing. | |||
b01.04 | Anti-clogging FWD./REV. Dead Time | 0.0~3600.0s | 1.0s | When anti-clogging is valid, b01.04 set the FWD./REV. transition time | |||
b01.05 | Maximum Transducer Setting Range | 0.0~100.0bar | 10.0bar | E.g. If the rated max. range of transducer is 10bar, b01.05 should be set to 10.0 | |||
b01.06 | AI1 Lower Limit | 0.00~10.00V | 1.00V | •Lower limit use to transducer zero setting •Higher limit use to accordant display and transducer pressure. •When display smaller than gauge, increase higher limit; When display greater than gauge, decrease higher limit. •When analog input is interfered, prolong filtering time so as to increase the ability of anti-interference, but decrease the sensitivity. •Corresponding relationship of transducer parameter setting: Figure6.1.1 Transducer parameters |
|||
b01.07 | Corresponding Setting of AI1 Lower Limit | -100.0~100.0% | 0.0% | ||||
b01.08 | AI1 Higher Limit | 0.00~10.00V | 5.00V | ||||
b01.09 | Corresponding Setting of AI1 Higher Limit | -100.0~100.0% | 100.0% | ||||
b01.10 | AI1 Filtering Time | 0.00~10.00s | 0.10s | ||||
b01.11 | AI2 Lower Limit | 0.00~10.00V | 1.00V | ||||
b01.12 | Corresponding Setting of AI2 Lower Limit | -100.0~100.0% | 0.0% | ||||
b01.13 | AI2 Higher Limit | 0.00~10.00V | 5.00V | ||||
b01.14 | Corresponding Setting of AI2 Higher Limit | -100.0~100.0% | 100.0% | ||||
b01.15 | AI2 Filtering Time | 0.00~10.00s | 0.10s | ||||
b01.16 | Restart After Power-on | 0~1 | 0 | 0: invalid 1: valid | |||
b01.17 | Control Mode | 0~1 | 1 | 0: Synchronous 1: Master-slave | |||
Br02 Group Application Function | |||||||
b02.00 | PID Source Selection | 0~1 | 0 | 0: Keypad 1: Reserved | |||
b02.01 | PID Feedback Source Selection |
0~1 | 0 | 0: AI1 1: Reserved | |||
b02.02 | PID Output Characteristics |
0~1 | 0 | 0: Water supply 1: Pumping | |||
b02.03 | Proportional Gain (KP) |
0.00~100.00 | 2.50 | Determining the strength of PID regulation, KP is bigger, regulation is stronger, but fluctuate easier too. | |||
b02.04 | Integral Coefficient (KI) | 0.00~10.00 | 1.00 | Bias between the feedback and the given, determining the speed of regulation, KI is bigger, regulation is stronger. | |||
b02.05 | Derivative Coefficient (KD) | 0.00~10.00 | 0.00 | Variable ratio between the feedback and the given, KD is bigger, regulation is stronger. Be cautious use, for differential regulation amplifies interference of system. | |||
b02.06 | Sampling Cycle (T) |
0.01~100.00s | 0.10s | Calculating time of regulator, when increased, response sluggishly. | |||
b02.07 | PID Control Bias Limit | 0.0~100.0% | 0.0% | Max. bias of PID output value corresponding to closed loop given value: Figure6.2.1 PID control curve Corresponding System Diagram of Max. Limit and Output Frequency. Properly set the value can regulate the accuracy and stability of PID system. |
|||
b02.08 | AI1 Feedback Lost Detecting Value |
0.0~100.0% | 1.0% | Transducer fault detecting setting value, corresponding to full range (100%), when the detecting time exceeds feedback lost time, it is deemed as malfunction by transducer, the system will report E022 as transducer fault code. |
|||
b02.09 | AI2 Feedback Lost Detecting Value |
0.0~100.0% | 0.0% | ||||
b02.10 | Feedback Lost Detecting time |
0.0~3600.0s | 1.0s | ||||
Br03 Group Application Function | |||||||
b03.00 | Communication Address | 0~31 | 02 | 00: Master controller 01~05: Auxiliary controller 06~31: Reserved |
|||
b03.01 | Baud Rate Selection | 0~5 | 3 | Data of master and slave comes into the rate. 0: 1200BPS 1: 2400BPS 2: 4800BPS 3: 9600BPS 4: 19200BPS 5: 38400BPS |
|||
b03.02 | Data Format | 0~5 | 0 | Data format (parity check) | |||
b03.03 | Communication Delay Time | 0~200ms | 15ms | Interval of data responding. | |||
b03.04 | Communication Timeout Delay 0.0: invalid | 0.0~100.0s | 0.0s | If the interval time exceeds the setting value, the system will report E018 as fault. | |||
b03.05 | Communication Error Action | 0~1 | 0 | 0: Halt and alarm 1: Don't alarm and continue |
|||
b03.06 | Communication Response Action | 0~1 | 0 | 0: Responding to write operation 1: Un-responding to writer operation |
|||
b03.07 | Data Transmission Time Interval | 0.05~2.00s | 0.10s | Ensure the effects of data transmission, long-time setting will slow down data transmission and short-time setting will easily make mistakes. | |||
b03.08 | Slave Quantity | 0~5 | 0 | 0: None | |||
b03.09 | Fault Shift | 0~2 | 2 | Fault Master Shift Invalid: Factory setting: 2 Valid: Master set as 0; Salve 1 set as 1. Remarks: Fault shift demands the salve 1 to connect a backup transducer. |
|||
Br04 Group Application Function | |||||||
b04.00 | Sleeping Function | 0~1 | 1 | No consuming auto stop. 0: Invalid 1: Valid |
|||
b04.01 | Sleeping Waiting Time | 0.0~300.0s | 5.0s | Delay time, seconds unit | |||
b04.02 | Sleeping Test | 0.0~10.0% | 4.0% | Water consuming test frequency rate. | |||
b04.03 | Wake-up Pressure Bias | 0.0~20.0bar | 0.5bar | During sleeping the wake-up pressure bias, e.g. the setting value (L)=3.0bar, bias (b04.03)=0.5bar, practical pressure (P)<L-0.5=2.5bar, the pump will restart again. | |||
b04.04 | Sleeping Bias | 0.0~1.0bar | 0.0bar | The pressure fluctuation which allows sleeping | |||
Br05 Group Application Function | |||||||
b05.00 | Water Level Control | 0~2 | 2 | Water level switch style, 0: invalid 1: NC 2: NO |
|||
b05.01 | Low Lever Restart Delay Time | 0~300min | 1min | Delay time of restart after water level switch recover. | |||
b05.02 | Terminal S1S2 Control | 0~3 | 2 | 0: Invalid 1: Electric contact control S1-COM on: Frequency rise S2-COM on: Frequency drop 2: Manual/auto control S2-COM off: Auto control S2-COM on: Manual control 3: Terminal run/stop S1-COM on: Run S1-COM off: Stop S2-COM off: Auto control S2-COM on: Manual control |
|||
b05.03 | Acceleration Time | 0.1~3600.0s | Model Set | The setting time from zero to max. frequency | |||
b05.04 | Deceleration Time | 0.1~3600.0s | Model Set | The setting time from max. frequency to zero | |||
b05.05 | Maximum Output Frequency | 10.00~600.00 Hz |
50.00Hz | Determine the Acc./Dec. rate | |||
b05.06 | Up limit of Output Frequency | b05.07~b05.05(Maximum Frequency) | 50.00Hz | Maximum running frequency | |||
b05.07 | Lower Limit of Output Frequency | 0.00Hz~b05.06 | 20.00Hz | The minimum running frequency of pump. | |||
b05.08 | Carrier Frequency | 1.0~15.0kHz | Model Set | Use to ameliorate the noise of motor and controller's interference to the surroundings. A high carrier makes a low motor noise, but leads to a big temperature rise and interference.Should not be altered if unnecessary. | |||
b05.09 | Low Pressure (LP) Restart Delay Time | 00~60min | 10min | In case of low pressure, b05.09≠0, the controller restarts to work according to the setting time automatically, without artificial restart. b05.09=0, restart invalid. | |||
b05.10 | Alternating Time | 0.00~300.00h | 8.00h | In order to balance and prolong the pump service life to set the parameter, unit: hour. When the parameter is set to 0.0, it means in-execution. Operational time of master and auxiliary pump switches over according to the setting alternating time. | |||
Br06 Group Application Function | |||||||
b06.00 | Running Status Display Selection | 0~0x1FF | 0x01F | bit0: Operational frequency bit1: The actual pressure of pump outlet bit2: The setting pressure of pump outlet bit3: Output current bit4: DC bus voltage bit5: Output voltage bit6: Present time bit7: The actual pressure of pump inlet bit8: Input terminal status |
|||
b06.01 | Stop Status Display Selection | 0~0x1FF | 0x00F | bit0: The setting pressure of pump outlet bit1: The actual pressure of pump outlet bit2: Giver frequency bit3: DC bus voltage bit4: Input terminal status bit5:Output terminal status bit6: AI1 input voltage bit7: The actual pressure of pump inlet bit8: Present time |
|||
b06.02 | Keypad Display Selection | 0~3 | 3 | 0: External keypad prior enable 1: Both display enable, only external keypad control; 2: Both display enable, only on board keypad control; 3: Both display enable and keypad control |
|||
b06.03 | Relay Output Selection | 0~5 | 0 | 0: Error or external fault 1: Forward running 2: Frequency reaching 3: Stop status 4: Lower limit of output frequency reaching 5: The frequency is not equal to zero |
|||
b06.04 | Third Latest Fault Type | Read Only | E000~E022 Refers to chapter 9. |
||||
b06.05 | Second Latest Fault Type | ||||||
b06.06 | Latest Fault Type | ||||||
b06.07 | Parameters Storage Condition | 0~2 | 0 | 0: Power-off storage 1: Power-off default storage 2: Invalid |
|||
b06.08 | Accumulated Running Time | 0~65535h | Read Only | Display accumulated running time | |||
b06.09 | Set the Password of b00.00 | 0~65535 | 65535 | Password set prevent user from modifying the parameters randomly, avoiding running abnormally and damages. | |||
Br07 Group Application Function | |||||||
b07.00 | Day-part Function Selection | 0~3 | 0 | 0: Invalid 1: Day-part A 2: Day-part A and B 3: Day-part A, B, C |
|||
b07.01 | Day-part A Starting Time | 00:00~24:00 | 00-00 | Setting starting time and finishing time to 0 is invalid. Pressure setting determines the steady state value of outlet pressure. Once actual pressure from inlet pipe network lower than inlet pressure lower limit, the pump stops. When regardless of the inlet water pressure, just set the lower limit as 0. |
|||
b07.02 | Day-part A Pressure Setting | 0.0~20.0bar | 3.0bar | ||||
b07.03 | Day-part A Finishing Time | 00:00~24:00 | 00-00 | ||||
b07.04 | AI2 Lower Limit of Day-part A | 0.0~20bar | 2.0bar | ||||
b07.05 | Day-part B Starting Time | 00:00~24:00 | 00-00 | ||||
b07.06 | Day-part B Pressure Setting | 0.0~20bar | 3.0bar | ||||
b07.07 | Day-part B Finishing Time | 00:00~24:00 | 00-00 | ||||
b07.08 | AI2 Lower Limit of Day-part B | 0.0~20.0bar | 3.0bar | ||||
b07.09 | Day-part C Starting Time | 00:00~24:00 | 00-00 | ||||
b07.10 | Day-part C Pressure Setting | 0.0~20.0bar | 3.0bar | ||||
b07.11 | Day-part C Finishing Time | 00:00~24:00 | 00-00 | ||||
b07.12 | AI2 Lower Limit of Day-part C | 0.0~20.0bar | 2.0bar | ||||
b07.13 | Lower Limit of Inlet Pressure | 0.0~100.0bar | 0.0bar | Valid all day, especially for the use of taking account of inlet water pressure. When not needed,, set as 0. | |||
b07.14 | Restore Defaults | 0~2 | 0 | 0: No action 1: Set to default 2: Clear error records |
|||
b07.15 | Password of Group Br08 | 0~65535 | 65535 | ||||
Br08 Group Application Function | |||||||
b08.00 | G/P Option | 0~1 | 1 | 0: G model 1: P model | |||
b08.01 | Motor Rated Power | 0.4~350kW | Model Set | Depend on model, setting parameters according to nameplate of motor | |||
b08.02 | Motor Rated Frequency | 0.00~600.00Hz | 50.00Hz | ||||
b08.03 | Motor Rated Speed | 0~36000RPM | Model Set | ||||
b08.04 | Motor Rated Voltage | 0~460V | |||||
b08.05 | Motor Rated Current | 0.0~2000.0A | |||||
b08.06 | Reserved | 0~65535 | 00000 | ||||
b08.07 | Set the Password of b07.15 | 0~65535 | 65535 | Modify password of b07.15 | |||
b08.08 | Password of Factory Parameters | 0~65535 | xxxxx | Don't try to enter or will cause abnormal operation and damages. |