Customization: | Available |
---|---|
Application: | Three Phase Transducer |
Output Type: | Triple |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model No. | Rated Input Voltage (V) | Input Current (A) | Maximum Output Current (A) | Motor Power (kW) | |
1Φ | 3Φ | ||||
B6031D(B2)-2001 | 1AC: 220V -15%~+15% |
8.2 | 7.0 | 0.37 | 0.75 |
B6031D(B2)-2002 | 14.2 | 11.0 | 0.75 | 1.5 | |
B6031D(B2)-2003 | 23.0 | 15.0 | 1.5 | 2.2 | |
B6031B2-4001 | 3AC: 380V -15%~+15% |
5.0 | 3.7 | / | 0.75 |
B6031B2-4002 | 5.8 | 5.0 | / | 1.5 | |
B6031B2-4003 | 8.0 | 7.0 | / | 2.2 | |
B6031B2-4005 | 12.0 | 11.0 | / | 4.0 | |
B6031B2-4007 | 18.0 | 16.0 | / | 5.5 | |
B6031B2-4010 | 21.0 | 20.0 | / | 7.5 |
Function Code | Name | Setting Range | Factory Setting | Description |
Br00 Group Application Function | ||||
b00.00 | Debugging password | 0~65535 | 00000 | Default is 00000 |
b00.01 | Constant Speed Operating Frequency | 000.0~600.00 | 50.00Hz | Constant speed operating frequency value |
b00.02 | Pressure Setting Value | 0.0~100.0bar | 3.0bar | Set according to the actual requirements of user |
b00.03 | Phase Selection | 0~1 | 1 | Single phase or three phase motor selection 0: three phase 1: single phase |
b0.04 | There Phase Motor Rotating Direction | 0~1 | 0 | 0: forward 1: reverse |
b00.05 | Restart After Power-on | 0~1 | 1 | 0: invalid 1: valid |
b00.06 | Frequency Instructions Selection | 0~6 | 5 | 0: constant speed 5: constant pressure water supply |
b00.07 | Maximum Transducer Setting Range | 0.0~100.0bar | 16.0bar | E.g. If the rated max. range of transducer is 10 bar, b00.07 should be set to10.0 |
b00.08 | High Water Pressure Alarm Value | 0.0~100.0bar | 10.0bar | When the pressure is higher than this preset value, the controller alarms, halts and displays "HP"; when the pressure is lower than this preset value, breakdown recover and running |
b00.09 | Low Water Pressure Alarm Value | 0.0~100.0bar | 0.0bar | When the pressure is lower than this preset value for a Low Pressure Running Time, the controller alarms, halts and displays "LP"; restart automatically from breakdown after 10 minutes' downtime. |
b00.10 | Low Pressure Running Time | 00~300s | 20s | |
b00.11 | Water Shortage Protection Factor | 0~100.0% | 30 | When the pump controller neither can pump the water after running a period of time (b00.13(s)+b00.20(s)+b00.21(s)), nor reported "A033" (digital display) fault, please turn up the b00.11 data, until it could reported "A033" fault. When reporting "A033" fault delay b00.12 can automatically restart, If b00.12=0, it could not restart after the water shortage fault. |
b00.12 | Latency Time to Restart After Water Shortage Protection | 0~30000min | 0 | |
b00.13 | Check the Running Time in State of Water Shortage |
01~60s | 20 | |
b00.14 | Restore Defaults | 0~2 | 0 | 0: No action 1: Set to default 2: Clear error records |
b00.15 | AI1 Lower Limit | -10.00~10.00V | 1.00V | • Currency type: 4~20mA, setting b00.15=1.00 Voltage type: 0.5~4.5v, setting b00.15=0.50; • Lower limit use to transducer Zero Setting |
b00.16 | AI1 Higher Limit | -10.00~10.00V | 5.00V | • Currency type: 4~20mA, setting b00.16=5.00, Voltage type: 0.5~4.5v, setting b00.16=4.50; • Higher limit use to accordant display and transducer pressure; • When display smaller than gauge, increase higher limit; • When display greater than gauge, decrease higher limit |
b00.17 | Proportional Gain (KP) | 0.00~100.00 | 3.50 | Determining the strength of PID regulation, KP is bigger, regulation is stronger, but fluctuate easier too. |
b00.18 | Wake-up Pressure Bias | 0.0~b0.02 (0.0~20.0bar) |
0.3bar | During sleeping the wake-up pressure bias, e.g. the setting value (L)=3.0Bar, Bias (b00.18)=0.3bar, practical pressure (P)<L-0.3=2.7bar, the pump will restart again. |
b00.19 | Sleeping Bias | 0.0~1.0bar | 0.1bar | The pressure fluctuation which allows sleeping. |
b00.20 | Acceleration Time | 0.1~3600.0s | 1s | The setting time from zero to max. Frequency |
b00.21 | Deceleration Time | 0.1~3600.0s | 1s | The setting time from max. Frequency to zero |
b00.22 | Maximum Output Frequency | b00.23~600.00Hz | 60.00Hz | Determine the Acc./Dec. rate |
b00.23 | Up limit of Output Frequency | b00.24~b00.22 (Maximum Frequency) | 60.00Hz | Maximum running frequency |
b00.24 | Lower Limit of Output Frequency | 0.00~b00.23 | 20.00Hz | The minimum running frequency of pump |
b00.25 | Latest Fault Type | E000~E022,LP,HP,A033 | ||
b00.26 | Motor Rated Voltage | 0~460V | 220V | |
b00.27 | Motor Rated Current | 0.0~2000.0A | Model Set | B6031D(B2)-2001 set to 7.0A; B6031D(B2)-2002 set to 11.0A; B6031D(B2)-2003 set to 15.0A; B6031B2-4001 set to 2.5A; B6031B2-4002 set to 5.0A; B6031B2-4003 set to 7.0A; B6031B2-4005 set to 11.0A; B6031B2-4007 set to 16.0A; B6031B2-4010 set to 20.0A |
b00.28 | Single Phase Motor Current Calibration Coefficients |
115~150% | 130% | When display current greater than actual current, decrease the coefficients; When display current smaller than actual current, increase the coefficients |
b00.29 | Freeze-proofing | 0~1 | 0 | Used in cold areas 0: invalid 1: valid |
b00.30 | Minimum Freeze-proofing Frequency | 1.00~30.00Hz (1.00~b00.24) |
5.00Hz | Be valid when b00.29 was set to 1, whenever sleeps, running with the setting frequency in case of freezing. |
b00.31 | Password of Group br01 | 0~65535 | 00000 | Don't try to enter or will cause abnormal operation and damages. |