Submersible Pump Motor Inverter with Water Shortage Protection and Constant Pressure Control

Application: Submerssible Motor
Nature of Source Flow: Passive inverter
Certification: ISO9001, CE
Output Power: 0.75kw-350kw
Brand: Infenion and FUJI
Grid Type: off-Grid Inverter
Samples:
US$ 150/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2009

Suppliers with verified business licenses

Rating: 5.0/5
Guangdong, China
Importers and Exporters
The supplier has import and export rights
Self-branded
The supplier has 2 Self-brands, check the Audit Report for more information
Patents Awarded
The supplier had awarded 4 patents, you can check the Audit Report for more information
Exhibition Experience
The supplier had participated in offline trade shows, you can check the Audit Report for more information
to see all verified strength labels (31)

Basic Info.

Model NO.
B6031iB2
Output Type
Triple
Circuit Topologies
Push-Pull Type
Nature of Wave String
Square Wave Inverter
Type
AC/DC/AC Inverter
Output T Type
Single/Triple Phase 220V
Power
0.75kw~350kw
Frequency
50Hz/60Hz
Phase
Single Phase 220V or 3 Phase 380V
Power Source
Electric Power
Transport Package
Pallet/Carton
Specification
CE
Trademark
BEDFORD
Origin
Guangzhou
HS Code
9032899099
Production Capacity
50000 Units/Month

Product Description

Company Profile
Guangzhou Bedford Electric Equipment Co., Ltd. which was established in April 2007 with the brand " BEDFORD", is a high-tech enterprise integrating with R&D, Production, Sales and Services together. The company's main products: all kinds of water pump inverter, solar photovoltaic inverter, general purpose vector control inverter; Variable Frequency pump, integrated intelligent water supply system, smart pump house and solar pumping system, etc. With software and hardware integration, intelligent control and remote monitoring platform combination, customize a variety of water pump energy saving control system for customers .
Submersible Pump Motor Inverter with Water Shortage Protection and Constant Pressure Control

Product Introduction

B6031I series products is specifically designed for deep well submersible pump, Some models controller can be set the parameter selection to control single-phase or three-phase pumps. A variety of special features: Single-phase, three-phase selection,Running automatically when power on,Sleep down when have no water consumption,The water-level of deep well and upper reservoir auto controlling,The water-level of deep well auto controlling and constant pressure water supply,Various of water supply fault alarm function,Many fault protection function.

Submersible Pump Motor Inverter with Water Shortage Protection and Constant Pressure ControlSubmersible Pump Motor Inverter with Water Shortage Protection and Constant Pressure ControlSubmersible Pump Motor Inverter with Water Shortage Protection and Constant Pressure ControlSubmersible Pump Motor Inverter with Water Shortage Protection and Constant Pressure ControlFault and Trouble Shooting
Fault Code Fault Type Reason Solution
LP Low water pressure
  1. Abnormal sensor;
  2. Motor rotates in the reverse direction;
  3. Insufficient water inflow;
  4. There is air inside the pump
  1. Check the installation of pressure transmitter;
  2. Check the motor whether rotates in right direction;
  3. Check the parameter b00.09 (setting value too big);
  4. Check the pump whether is vent out the air inside
HP High water pressure
  1. Abnormal sensor;
  2. The parameter b00.08 setting value is too small
  1. Check the installation of pressure transmitter;
  2. Check the parameter b00.08 (setting value too small)
E022 Sensor fault
  1. Pressure transmitter disconnected;
  2. Wrong pressure transmitter wiring;
  3. Pressure transmitter short circuit;
  4. Pressure transmitter break down
  1. Check the cable between pressure transmitter and controller;
  2. Check the sensor whether is normal
A033 Water shortage fault
  1. No water in the deep well
  2. Water-level sensors in the deep well is broken
  1. Check whether there is water in the deep well
  2. Check whether the water-level sensors is broken.

Controller Running Fault and Trouble Shooting
Fault Code Fault Type Reason Solution
E001 IGBT Ph-U Fault (OUT1)
  1. Acc/Dec time is too short;
  2. IGBT module fault;
  3. Malfunction caused by interference;
  4. Grounding is not properly
  1. Increase Acc/Dec time;
  2. Check external equipments and eliminate interference;
  3. Ask supplier for support
E002 IGBT Ph-V Fault (OUT2)
E003 IGBT Ph-W Fault (OUT3)
E004 Over-current When Acceleration (OC1)
  1. Acc time is too short;
  2. Low input voltage;
  3. The power of controller is small
  1. Prolong Acc time;
  2. Check the power supply;
  3. Select bigger power controller
E005 Over-current When Deceleration (OC2)
  1. Dec time is too short;
  2. Load is too heavy;
  3. The power of controller is small
  1. Prolong Dec time;
  2. Increase braking unit;
  3. Select bigger capacity controller
E006 Over-current When Constant Speed Running (OC3)
  1. Sudden change of load;
  2. Low input voltage;
  3. The power of controller is small
  1. Check the load;
  2. Check the power supply;
  3. Select bigger capacity controller
E007 Over-voltage When Acceleration (OV1)
  1. High input voltage;
  2. Regenerative energy from the motor is too large
  1. Check the power supply;
  2. Avoid to restart the motor until it stop running completely
E008 Over-voltage When Deceleration (OV2)
  1. Dec time is too short;
  2. Load is too heavy;
  3. High input voltage
  1. Increase Dec time;
  2. Increase braking unit;
  3. Check the power supply
E009 Over-voltage When Constant Speed Running (OV3)
  1. High input voltage;
  2. Load is too heavy
  1. Install input reactor;
  2. Increase braking unit
E010 DC Bus Under-voltage (UV)
  1. Low input voltage
  1. Check the grid's input power supply
E011 Motor Overload (OL1)
  1. Low input voltage;
  2. Wrong setting of motor parameter;
  3. Motor locked-rotor or sudden big change of load to small load;
  4. The power of motor is too small
  1. Check the power supply;
  2. Set the rated current of motor properly;
  3. Check the load, adjust the value of torque boost;
  4. Select proper power motor
E012 Controller Overload (OL2)
  1. Acc time is too short;
  2. Restart the motor when it is decelerating;
  3. Low input voltage;
  4. Load is too heavy
  1. Prolong Acc time;
  2. Avoid to restart the motor until it stop running completely;
  3. Check the power supply;
  4. Select bigger capacity controller
E013 Input Phase Failure (SPI)
  1. Open-phase occurred in power supply
  1. Check the wiring, installation and the power supply
E014 Output Phase Failure (SPO)
  1. Open-phase occurred at output side of main circuit
  1. Check the output wiring, cable and motor
E015 Rectify Overheat (OH1)
  1. Sudden over-current;
  2. Input/output side has short circuit;
  3. Cooling fans of controller stopped or damaged;
  4. Ambient temperature is too high;
  5. Wires or connectors of control board are loose;
  6. Auxiliary power supply unit is damaged or low driving voltage for IGBT;
  7. Power module bridge is damaged;
  8. Control board is abnormal
  1. Refer to measures of over-current;
  2. Check the wiring;
  3. Replace cooling fans;
  4. Decrease the ambient temperature;
  5. Check and reconnect;
  6. Ask supplier for support
E016 IGBT Overheat (OH2)
E018 Reserve    
E019 Current Detection Fault (ITE)
  1. Wires or connectors of control board are loose;
  2. Auxiliary power supply unit is damaged;
  3. Current detector is damaged or amplifying circuit is abnormal
  1. Check the wiring and connectors;
  2. Ask supplier for support
E020 Reserve    
E021 EEPROM Fault (EEP)
  1. R/W fault of control parameters
  1. Press STOP/RST to reset;
  2. Ask for support


Package and Shipping